Directives and standards
3
EU directives
Methods of completion of unsetting (BS 8243:2010 - Clause 6.4)
3.1.5.3.2
24
Vanderbilt
Tamper
An EXIT TERMINATOR zone type must be configured for SPC.
Refer to the following section in this manual:
Zone types [➙ 347]
b) Push button switch mounted outside the supervised premises
Connect the push button into an SPC zone input as follows:
An EXIT TERMINATOR zone type must be configured for SPC.
Refer to the following section in this manual:
Zone types [➙ 347]
c) Protective switch (i.e. door contact) fitted to the final exit door of the alarmed
premises or area
Connect the switch to the SPC System as follows:
The contact is fitted to the final exit door and is connected to an ENTRY/EXIT zone
with a 'Final Exit' attribute.
Refer to the following section in this manual:
Zone types [➙ 347]
Zone attributes [➙ 350]
A misoperation signal is possible using the alarm abort feature. This is enabled by
default.
Refer to the following section in this manual:
OPTIONS [➙ 111] (Kypad)
Options [➙ 222] (Browser)
d) Digital key
Not supported by SPC.
e) In conjunction with an ARC
This method of setting is supported by using SPC COM XT or other third party
ARC software using EDP commands.
Unsetting methods are complied with as follows:
Installation & Configuration Manual
A6V10276959
01.05.2016