Vanderbilt SPC42 Series Installation & Configuration Manual page 115

Hide thumbs Also See for SPC42 Series:
Table of Contents

Advertisement

Vanderbilt
Timer
Description
FINAL EXIT
is closed. (1 – 45 seconds)
Bell on Fullset
Activates the external bell momentarily to indicate a full set
condition. (0 – 10 seconds)
FULLSET BELL
Strobe on Fullset
Activates the strobe on the external bell momentarily to
indicate a full set condition. (0 – 10 seconds)
FULLSET STROBE
Fail To Set
Number of seconds to display fail to set message on keypads
(0 until valid PIN is entered). (0 – 999 seconds)
FAIL TO SET
Alarm
Double Knock
The maximum delay between activation's of zones with the
double attribute, which will cause an alarm. (1 – 99 seconds)
DKNOCK DELAY
Soak
The number of days a zone remains under soak test before it
automatically returns to normal operation. (1 – 99 days)
SOAK DAYS
Seismic Test Interval
The average period between seismic sensor automatic tests
(12 – 240 hours)
SEISMIC AUTOTEST
Note: To enable automatic testing, the Automatic Sensor Test
attribute must be enabled for a seismic zone.
Seismic Test Duration
Maximum time (in seconds) that a seismic sensor takes to
trigger an alarm in response to the 'Seismic Test' output.
SEISMIC TEST DUR
(3 - 120 seconds)
Lockout Post Alarm
Duration after alarm that access will be denied.
LOCKOUT POST
ALARM
External Bell Strobe
Duration that the strobe output will be active when an alarm is
activated. (1 – 15 minutes; 0 = indefinitely)
STROBE TIME
Alerts
Mains Delay
The time after a mains fault has been detected before an alert
is activated by the system. (0 – 60 minutes)
MAINS SIG DELAY
Engineer
Engineer Access
The timer for the Engineer access starts as soon as the user
enables the Engineer Access. (0 – 999 minutes. '0' indicates
ENGINEER ACCESS
no time limitation for system access)
Engineer auto log out
Duration of inactivity after which the engineer will be
automatically locked out
ENG AUTO LOG OUT
Keypad
Keypad Timeout
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10 – 300 seconds)
KEYPAD TIMEOUT
Keypad Language
The duration a keypad will wait in idle before switching
language to default ( 0 - 9999 seconds; 0 = never).
KEYPAD LANGUAGE
Fire
Fire Pre-alarm
Number of seconds to wait before reporting fire alarm for
zones with 'Fire pre-alarm' attribute set. (1 – 999 seconds)
FIRE PRE-ALARM
See Editing a Zone [➙ 237].
Fire recognition
Extra time to wait before reporting file alarm for zones with
'Fire pre-alarm' and 'Fire Recognition' attributes set. (1 – 999
FIRE RECOGNITION
seconds). See Editing a Zone [➙ 237].
PIN
PIN Valid
Period for which pin is valid in days ( 1 - 330 )
PIN VALID
PIN Changes Limit
Number of changes within a valid period ( 1 - 50 )
PIN CHANGES LIMIT
PIN Warning
Time before PIN expiry after which a warning will be
displayed
PIN WARN
( 1 - 14 )
Installation & Configuration Manual
Engineer programming via the keypad
16
Timers
Default
0 sec.
0 sec.
10 sec.
10 sec.
14 days
168 hours.
30 sec.
0 mins
15 min.
0 min.
0 min.
0 mins.
30 sec.
10 secs
30 sec.
120 sec.
30 days
5
5 days
115