Vanderbilt SPC42 Series Installation & Configuration Manual page 231

Hide thumbs Also See for SPC42 Series:
Table of Contents

Advertisement

Vanderbilt
Timer
Description
External Bell Delay
This will cause a delayed activation of the external bell. (0 –
600 seconds)
EXT BELL DELAY
Chime
Number of seconds that a chime output will activate, when a
zone with chime attribute opens. (1 – 10 seconds)
CHIME TIME
Confirmation
Confirm
CONFIRM TIME
This timer applies to the alarm confirmation feature and is
defined as the maximum time between alarms from two
different non overlapping zones that will cause a confirmed
alarm. (30 – 60 minutes)
Confirmed holdup
This timer applies to the confirmed holdup feature and is
defined as the maximum time between alarms from two
different non-overlapping zones that will cause a confirmed
alarm. (480 - 1200 minutes)
Dialer Delay
When programmed, the dialler delay initiates a predefined
delay period (0 -30 seconds) before the system dials out to an
DIALER DELAY
Alarm Receiving Centre (ARC). This is specifically designed
to reduce unwarranted responses from Alarm Receiving
Centres and the constabulary. In the event of a subsequent
zone being tripped the dialler delay period is ignored and the
dialler dials out immediately. (0 – 30 seconds)
Alarm abort
Time after a reported alarm in which an alarm abort message
can be reported. (0 – 999 seconds))
ALARM ABORT
Setting
Setting Authorisation
Period for which Setting Authorisation is valid. Enter a value
between 10 and 250 seconds.
SETTING AUTH
Final Exit
The Final Exit time is the number of seconds that arming is
delayed after a zone programmed with the final exit attribute
FINAL EXIT
is closed. (1 – 45 seconds)
Bell on Fullset
Activates the external bell momentarily to indicate a full set
condition. (0 – 10 seconds)
FULLSET BELL
Strobe on Fullset
Activates the strobe on the external bell momentarily to
indicate a full set condition. (0 – 10 seconds)
FULLSET STROBE
Fail To Set
Number of seconds to display fail to set message on keypads
(0 until valid PIN is entered). (0 – 999 seconds)
FAIL TO SET
Alarm
Double Knock
The maximum delay between activation's of zones with the
double attribute, which will cause an alarm. (1 – 99 seconds)
DKNOCK DELAY
Soak
The number of days a zone remains under soak test before it
automatically returns to normal operation. (1 – 99 days)
SOAK DAYS
Seismic Test Interval
The average period between seismic sensor automatic tests
(12 – 240 hours)
SEISMIC AUTOTEST
Note: To enable automatic testing, the Automatic Sensor Test
attribute must be enabled for a seismic zone.
Seismic Test Duration
Maximum time (in seconds) that a seismic sensor takes to
trigger an alarm in response to the 'Seismic Test' output.
SEISMIC TEST DUR
(3 - 120 seconds)
Lockout Post Alarm
Duration after alarm that access will be denied.
LOCKOUT POST
ALARM
External Bell Strobe
Duration that the strobe output will be active when an alarm is
activated. (1 – 15 minutes; 0 = indefinitely)
STROBE TIME
Alerts
Installation & Configuration Manual
Engineer programming via the browser
Note: Only available when Security Grade is
'Unrestricted' and 'DD243' is selected for 'Confirmation'
variable. (See System Options [➙ 222])
17
Configuration
Default
0 sec.
2 sec.
30 min.
480 min.
30 sec.
30 sec.
20 secs
7 sec.
0 sec.
0 sec.
10 sec.
10 sec.
14 days
168 hours.
30 sec.
0 mins
15 min.
231
A6V10276959
01.05.2016

Hide quick links: