Vanderbilt SPC42 Series Installation & Configuration Manual page 174

Hide thumbs Also See for SPC42 Series:
Table of Contents

Advertisement

Engineer programming via the browser
17
Panel status
174
Vanderbilt
Description
Text description of the door controller (max. 16 characters).
Type
The type of expander detected (=door controller).
S/N
The serial number of the door controller.
Version
The firmware version of the door controller.
Comms
The status of the door controller (online or offline).
Status
The status of the door controller (OK, Fault).
PSU
Specifies if the door controller has a PSU.
Performable actions
Refresh
Click on the refresh button to update the status of the system alerts.
To view more status information:
Click on a door controller's identifying parameters (ID, description, type, serial
number) to display further status details.
Communication
The physical status (OK, Fault) and the programmed status (OK, Isolated,
Inhibited) of the keypad cable connection to the expander.
Cabinet Tamper
The physical and programmed status of the expander cabinet tamper.
Fuse Fault
The physical and programmed status of the door controller fuse.
Code Tamper
Status of the user's PIN. Multiple failed attempts result in an alert.
Performable actions
Restore Alerts
Click the button to restore all alerts on the panel.
Inhibit
Click this button to inhibit a fault condition. The inhibit operation will disable
that fault or zone for one arming period only.
Inhibit operation is not available in Security Grade EN 50131 Grade 3.
Isolate
Click this button to isolate that zone. Isolating a zone will de-activate that zone
until such time as the zone is explicitly de-isolated again. It is recommended
that you exercise caution when isolating zones as those zones will not be
active every time the system is SET.
Installation & Configuration Manual
A6V10276959
01.05.2016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents