Channel 2 output status
Table A- 119 Channel 2 output status
Modbus
Data type /
register
Size in bytes
8864
Unsigned / 2
8865
Unsigned / 2
Channel 2 output frequency
Table A- 120 Channel 2 output frequency
Modbus
Data type /
register
Size in bytes
8905
Unsigned / 2
8906
Float / 4
Channel 2 output pulse
Table A- 121 Channel 2 output pulse
Modbus
Data type /
register
Size in bytes
8973
Unsigned / 2
8978
Float / 4
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Parameter
Description
Simulation
Enables or disables
simulation of channel 2
output status.
Simulated value Signal level that is
output on the channel
when simulation is
enabled.
Parameter
Description
Simulation
Enables or disables
simulation of channel 2
output frequency.
Simulated value Frequency value that is
output on the channel
when simulation is
enabled.
Parameter
Description
Simulation
Enables or disables
simulation of channel 2
output pulses.
Simulated value Pulse frequency value
that is output on the
channel when simula-
tion is enabled.
A.9 Modbus holding registers tables
Default value
Value range /
[unit]
Setting options
(unit register)
0
0: Disabled
•
1: Enabled
•
0
0, 1
Default value
Value range /
[unit]
Setting options
(unit register)
0
0: Disabled
•
1: Enabled
•
1.0
0.0 - 12500.0
[Hz]
Default value
Value range /
[unit]
Setting options
(unit register)
0
0: Disabled
•
1: Enabled
•
0.0
0.0 - 12500.0
[pulses/s]
Modbus communication
Access
level
Read /
write
Read /
write
Access
level
Read /
write
Read /
write
Access
level
Read /
write
Read /
write
323