Siemens SITRANS F series Operating Instructions Manual page 206

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F series:
Table of Contents

Advertisement

Modbus communication
A.9 Modbus holding registers tables
Modbus
Data type /
register
Size in bytes
10066
Float / 4
8807
Float / 4
8814
Unsigned / 2
8815
Float / 4
7146
Float / 4
8886
Float / 4
8888
Float / 4
204
Parameter
Description
Lower range
Lower rate of change
value ROC
value that is mapped to
the lower nominal
range boundary se-
lected by current mode
(8806). Applicable if
Process value (8802) =
36.
Damping value
Time constant of
damping filter for cur-
rent output signal.
Fail-safe behav-
Current output reaction
ior
in case of a fault.
Fail-safe value
Output value in case of
a fault and when Fail-
safe behavior (8814) is
configured to 4.
Forced value
Forced value when
forcing is active.
Offset adjust-
Command to trim the
ment
lower range value of
the loop current.
Simulate a loop current
of 4.0 mA, measure the
current with an ampere
meter and write the
measured value to this
register.
Gain adjust-
Command to trim the
ment
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an
ampere meter and
write the measured
value to this register.
Default value
Value range /
[units]
Setting options
(units regis-
ter)
0.0
-
[m/s²]
(8564)
0.0
0.0 - 100.0
[s]
0
0: Lower fault current
1: Upper fault current
2: Last valid value
3: Disabled
4: Custom value
0.0
0.0 - 25.0
[mA]
4.0
3.5 - 25.0
[mA]
[mA]
0.0 - 25.0
[mA]
0.0 - 25.0
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Write
only
Write
only