Modbus
Data type /
register
Size in bytes
8910
Unsigned / 2
8935
Float / 4
8937
Float / 4
8915
Float / 4
8917
Float / 4
8911
Float / 4
8913
Float / 4
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Parameter
Description
Flow direction
Flow direction filter
applicable for Process
values (8904) set to 0,
1, 19, or 27.
Frequency
Upper frequency value.
value high
Upper nominal output
range boundary.
Frequency
Lower frequency value.
value low
Lower nominal output
range boundary.
Upper range
Upper volume flow
value volume
value that is mapped to
flow
the upper nominal
range boundary se-
lected by Frequency
value high (8935).
Applicable if Process
value (8904) = 1.
Lower range
Lower volume flow
value volume
value that is mapped to
flow
the lower nominal
range boundary se-
lected by Frequency
value low (8937). Ap-
plicable if Process
value (8904) = 1.
Upper range
Upper mass flow value
value mass flow
that is mapped to the
upper nominal range
boundary selected by
Frequency value high
(8935). Applicable if
Process value (8904) =
0.
Lower range
Lower mass flow value
value mass flow
that is mapped to the
lower nominal range
boundary selected by
Frequency value low
(8937). Applicable if
Process value (8904) =
0.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units regis-
ter)
0
0: Positive direction
1: Negative direction
2: Positive and nega-
tive directions
3: Positive and nega-
tive directions (sym-
metric mode)
10000.0
0.0 - 12500.0
[Hz]
0.0
0.0 - 12500.0
[Hz]
0.4 % • max.
-
volume flow
[m
/s]
3
(7500)
0.0
-
[m
/s]
3
(7500)
0.2 • max.
-
mass flow-
[kg/s]
(7400)
0.0
-
[kg/s]
(7400)
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write