Modbus
Data type /
register
Size in bytes
9440
Float / 4
7163
Float / 4
Channel 4 pulse output settings
Table A- 63
Channel 4 pulse output settings
Modbus
Data type /
register
Size in bytes
9460
Unsigned / 2
9462
Unsigned / 2
9465
Float / 4
9463
Float / 4
9467
Float / 4
10255
Unsigned / 2
9474
Float / 4
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Parameter
Description
Fail-safe value
Output value in case of
a fault and when Fail-
safe behavior (9439) is
configured to 4.
Forced value
Forced value when
forcing is active.
Parameter
Description
Process value
Select process value
for the pulse output.
Flow direction
Flow direction filter.
Amount of vol-
Amount value to gen-
ume
erate an output pulse.
Applicable if process
value (9460) is set to 1.
Amount of
Amount value to gen-
mass
erate an output pulse.
Applicable if process
value (9460) is set to 0.
Amount of
Amount value to gen-
standard vol-
erate an output pulse.
ume
Applicable if process
value (9460) is set to
27.
Pulses per
Number of pulses
amount
which will be output
when configured
amount is reached.
Pulse width
Pulse duration.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units regis-
ter)
0.0
0.0 - 12500.0
[Hz]
1.0
0.0 - 12500.0
[Hz]
Default value
Value range /
[units]
Setting options
(units regis-
ter)
0
0: Mass flow
1: Volume flow
27: Standard volume
flow rate (only hydro-
carbon and gas ap-
plications)
0
0: Positive direction
1: negative direction
2: Positive and nega-
tive directions
0.001
-
[m
]
3
(8993)
1.0
-
[kg]
(8992)
1.0
-
[Sl]
(8994)
1
-
0.1
0.00004 - 4.0
[s]
Modbus communication
Access
level
Read /
write
Read /
write
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write