Modbus communication
A.9 Modbus holding registers tables
Process value 2
Table A- 110 Process value 2
Modbus
Data type /
register
Size in bytes
11201
Unsigned / 2
11262
Float / 4
11264
String / 32
11244
Float / 4
11246
String / 32
11205
Unsigned / 2
316
Parameter
Description
Process value
Process value config-
ured to be monitored
Maximum value Drag indicator of max-
imum value specified
by Process value
(11201)
Maximum value
Shows timestamp of
timestamp
recorded maximum
value specified by
Process value (11201)
Minimum value
Drag indicator of mini-
mum value specified
by Process value
(11201)
Minimum value
Shows timestamp of
timestamp
recorded minimum
value specified by
Process value (11201)
Reset logging
Command to reset the
drag pointers to the
process value's default
value.
Default value
Value range /
[unit]
Setting options
(unit register)
Disabled
3000: Volume flow
•
3004: Mass flow
•
3006: Sound velocity
•
3008: Flow velocity
•
3040: Density
•
3042: Medium tem-
•
perature
3044: Pressure
•
3046: Viscosity
•
3048: RTD tempera-
•
ture 1
3050: RTD tempera-
•
ture 2
65535: Disabled
•
Min. floating
-
point value
[units depend-
ing on pro-
cess value]
-
Max. floating
-
point value
[units depend-
ing on pro-
cess value]
-
-
1: Reset
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Access
level
Read /
write
Read
only
Read
only
Read
only
Read
only
Write
only