Siemens SITRANS F series Operating Instructions Manual page 255

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F series:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
9419
Float / 4
9421
Float / 4
9423
Float / 4
9425
Float / 4
9427
Float / 4
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Parameter
Description
Upper range
Upper process density
value density
value that is mapped to
the upper nominal
range boundary se-
lected by Frequency
value high (9435).
Applicable if Process
value (9404) = 2.
Lower range
Lower process density
value density
value that is mapped to
the lower nominal
range boundary se-
lected by Frequency
value low (9437). Ap-
plicable if Process
value (9404) = 2.
Upper range
Upper medium tem-
value tempera-
perature value that is
ture
mapped to the upper
nominal range bounda-
ry selected by Fre-
quency value high
(9435). Applicable if
Process value (9404) =
3.
Lower range
Lower medium tem-
value tempera-
perature value that is
ture
mapped to the lower
nominal range bounda-
ry selected by Fre-
quency value low
(9437). Applicable if
Process value (9404) =
3.
Upper range
Upper standard volume
value standard
flow value that is
volume flow
mapped to the upper
nominal range bounda-
ry selected by Fre-
quency value high
(9435). Applicable if
Process value (9404) =
27.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units regis-
ter)
Max. density
-
[kg/m
]
3
(7600)
0.08
-
[kg/m
]
3
(7600)
Max. medium
-
temperature
[°C]
(7700)
Min. medium
-
temperature
[°C]
(7700)
0.4 % • max.
-
standard
volume flow
[Sm
/h]
3
(7964)
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
253