Modbus communication
A.9 Modbus holding registers tables
Process value 4
Table A- 112 Process value 4
Modbus
Data type /
register
Size in bytes
11203
Unsigned / 2
11334
Float / 4
11336
String / 32
11316
Float / 4
11318
String / 32
11207
Unsigned / 2
318
Parameter
Description
Process value
Process value config-
ured to be monitored
Maximum value Drag indicator of max-
imum value specified
by Process value
(11203)
Maximum value
Shows timestamp of
timestamp
recorded maximum
value specified by
Process value (11203)
Minimum value
Drag indicator of mini-
mum value specified
by Process value
(11203)
Minimum value
Shows timestamp of
timestamp
recorded minimum
value specified by
Process value (11203)
Reset logging
Command to reset the
drag pointers to the
process value's default
value.
Default value
Value range /
[unit]
Setting options
(unit register)
Disabled
3000: Volume flow
3004: Mass flow
3006: Sound velocity
3008: Flow velocity
3040: Density
3042: Medium tem-
perature
3044: Pressure
3046: Viscosity
3048: RTD tempera-
ture 1
3050: RTD tempera-
ture 2
65535: Disabled
Min. floating
-
point value
[units depend-
ing on pro-
cess value]
-
Max. floating
-
point value
[units depend-
ing on pro-
cess value]
-
-
1: Reset
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Access
level
Read /
write
Read
only
Read
only
Read
only
Read
only
Write
only