Siemens SITRANS F series Operating Instructions Manual page 267

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F series:
Table of Contents

Advertisement

Modbus
Data type /
register
Size in bytes
10635
Float / 4
10641
Float / 4
10647
Float / 4
10620
Float / 4
10608
Float / 4
10610
Float / 4
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Parameter
Description
Fail-safe value
Input value in case of a
temperature
fault and when Fail-
safe behavior config-
ured to 1. Applicable if
process value (10623)
= 1.
Fail-safe value
Input value in case of a
density
fault and when Fail-
safe behavior config-
ured to 1. Applicable if
process value (10623)
= 2.
Fail-safe value
Input value in case of a
viscosity
fault and when Fail-
safe behavior config-
ured to 1. Applicable if
process value (10623)
= 3.
Trimmed input
Provides the measured
value
current value.
Offset adjust-
Command to trim the
ment
lower range value of
the analog input.
Provide a loop current
of 4.0 mA, read out the
value of Trimmed input
value and write the
value to this register.
Gain adjust-
Command to trim the
ment
upper range value of
the loop current.
Simulate a loop current
of 20.0 mA, measure
the current with an
ampere meter and
write the measured
value to this register.
A.9 Modbus holding registers tables
Default value
Value range /
[units]
Setting options
(units regis-
ter)
Min. medium
-
temperature
[°C]
(7700)
0.08
-
[kg/m
]
3
(7600)
0.0
-
[m
/s]
2
(7524)
-
-
-
-
-
-
Modbus communication
Access
level
Read /
write
Read /
write
Read /
write
Read
only
Write
only
Write
only
265

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fst030