Siemens SITRANS F series Operating Instructions Manual page 212

Ultrasonic flowmeters
Hide thumbs Also See for SITRANS F series:
Table of Contents

Advertisement

Modbus communication
A.9 Modbus holding registers tables
Modbus
Data type /
register
Size in bytes
10032
Float / 4
10034
Float / 4
10036
Float / 4
10038
Float / 4
10040
Float / 4
210
Parameter
Description
Upper range
Upper dimensionless
value dimen-
value that is mapped to
sionless
the upper nominal
range boundary se-
lected by Frequency
value high (8935).
Applicable if Process
value (8904) = 28, 32,
33, 34, or 36.
Lower range
Lower dimensionless
value dimen-
value that is mapped to
sionless
the lower nominal
range boundary se-
lected by Frequency
value low (8937). Ap-
plicable if Process
value (8904) = 28, 32,
33, 34, or 36.
Upper range
Upper current value
value current
that is mapped to the
upper nominal range
boundary selected by
Frequency value high
(8935). Applicable if
Process value (8904) =
25 or 26.
Lower range
Lower current value
value current
that is mapped to the
lower nominal range
boundary selected by
Frequency value low
(8937). Applicable if
Process value (8904) =
25 or 26.
Upper range
Upper process viscosi-
value viscosity
ty value that is mapped
to the upper nominal
range boundary se-
lected by Frequency
value high (8935).
Applicable if Process
value (8904) = 21 or
29.
Default value
Value range /
[units]
Setting options
(units regis-
ter)
1.0
-
0.0
-
20.0
-
[mA]
4.0
-
[mA]
1.0
-
[m²/s]
(7524)
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fst030