Modbus communication
A.9 Modbus holding registers tables
Modbus
Data type /
register
Size in bytes
8899
Unsigned / 2
8842
Unsigned / 4
8844
Unsigned / 4
8848
Unsigned / 4
8850
Unsigned / 4
8856
Unsigned / 4
10056
Unsigned / 4
214
Parameter
Description
NAMUR status
Bit encoded selection
signals
of NAMUR status sig-
nals which impacts the
status output.
Applicable if Status
mode = 0. NAMUR
status is derived from
Alarm class (8858).
Alarm items 1
Bit encoded selection
of alarm items that
impact the output.
Mainly sensor alarms.
See Alarm items
(Page 295). Applicable
if Status mode = 1.
Alarm items 2
Bit encoded selection
of alarm items that
impact the output.
Mainly sensor alarms.
See Alarm items
(Page 295). Applicable
if Status mode = 1.
Alarm items 4
Bit encoded selection
of alarm items that
impact the output. See
Alarm items
(Page 295). Applicable
if Status mode = 1.
Alarm items 5
Bit encoded selection
of alarm items that
impact the output. See
Alarm items
(Page 295). Applicable
if Status mode = 1.
Alarm items 8
Bit encoded selection
of alarm items that
impact the output. See
Alarm items
(Page 295). Applicable
if Status mode = 1.
Alarm items 9
Bit encoded selection
of alarm items that
impact the output. See
Alarm items
(Page 295). Applicable
if Status mode = 1.
Default value
Value range /
[units]
Setting options
(units regis-
ter)
0
Bit 0: Out of specifi-
cation (PA, PW)
Bit 1: Failure (MA)
Bit 2: Maintenance
required (MR, MD)
Bit 3: Function check
(FC)
0
0
0
0
0
0
SITRANS F Ultrasonic flowmeters FST030 (Modbus)
Operating Instructions, 08/2017, A5E37367739-AC
Access
level
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write
Read /
write