LS10143-001SK-E
5.
From the next screen, add an ECS-AMP.
The screen will display "Adding module [#]..." for a few moments. You will be
returned to the <New Module Type> screen where you can select another a name
for the module(s) if desired.
You must save changes when you exit the Program Menu or the new module will not be added. For more
information see section 9.2.2.
If you Add a Module that has not been physically connected, the panel will go into trouble after it re-initializes
(when you exit the Program Menu with changes accepted). When the new module is attached, the trouble will
restore automatically the next time you power up the FACP.
11.5.2

Editing an Amplifier

When editing AMPs, the features that may be edited are: module ID, module name, amplifier mod, ECS-CE4
installed (Yes or No), and output voltage. To edit an existing module:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow key to select the module you wish to edit.
6.
Press the right arrow key

11.6 LOC Programming

LOC Priority is a programmable option for the following ECS devices:
ECS-VCM
ECS-NVCM
ECS-RVM
11.6.1

Adding an LOC

To add new LOCs to the system, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming menu.
3.
Press 1 to enter Module menu.
4.
Press 2 to add a module.
5.
From the next screen, add either an ECS-VCM or ECS-NVCM* or ECS-RVM**.
* Only 1 ECS-VCM or ECS-NVCM may be installed per site.
** Up to 15 ECS-RVMs may be installed per site.
The screen will display "Adding module [#]..." for a few moments. You will be
returned to the <New Module Type> screen where you can select another a name
for the module(s) if desired.
ENTER to move to next selection.