LS10143-001SK-E
2.
From the list that displays, press ENTER to select the module where this point is located. The screen that
displays will show you if the point has a trouble and will provide sensitivity compliance information. (See
Section 10.4.11 for complete information about detector sensitivity compliance.)

10.4.13 View Alarms or Troubles

When the system is in alarm or trouble, you can press

10.4.14 System Information

1.
From the Main Menu, press 8 to access the System Information menu.
About Panel
Press 1 to access About Panel to view the panel model, serial number and system version number and date.

Send/Receive firmware updates

The IFP-2100/ECS or RFP-2100 has the ability to be updated in the field. The latest IFP-2100/ECS or RFP-2100
Firmware Update Utility can be downloaded from the Farenhyt Web Site. Once a panel has been updated using
the Firmware Update Utility, you can use Send/Receive firmware updates to propagate the firmware to the other
panels in the network.
1.
Press 2 to send a firmware update or press 3 to receive a firmware update from the System Information
menu. Available panels are listed in the menu.
2.
Use the up or down arrow key to select a panel to send/receive an update to/from. Press ENTER to start the
update process.

Feature Activation

This menu is used to activate/register additional features.
1. Press 4 from the System Information menu. This will bring up the Feature Activation menu.
2. Press 1 to enter a six digit activation code or press 2 to review features already activated in this panel.
Ethernet Info
1.
Press 5 from the System Information menu for Ethernet Information.
AlarmNet Info
1.
Press 6 from the System Information menu for AlarmNet Info
2.
Cell Strength: 0 to 100%
3.
Status: Registered/Not Registered
to view the location of an alarm or trouble.