Advertisement

Model IFP-2100/ECS Installation Manual
the drill.
10.4.5

Conduct an Indicator Test

The indicator test checks the annunciator LEDs, PZT, and LCD display.
1.
From the Main Menu, press 1 for System Tests.
2.
Press 2 for Indicator Test. The system turns on each LED several times, beeping the PZT as it does so. At the
same time it scrolls each available character across the LCD. A problem is indicated if any of the following
occurs:
An LED does not turn on.
You do not hear a beep.
All four lines of the LCD are not full.
This test will run for approximately 15 minutes or until the user manually exits. You can press any key to end
manually while the test is still in progress. When the test ends, you will be returned to the <Test Menu>.
10.4.6

Conduct a Walk Test

Walk Test is a feature which allows one person to test the fire alarm system. The Walk Test will run for 4 hours
or until the user manually exits. If an alarm or pre-alarm condition is occurring in the system, you will not be able
to enter the walk test. A walk test may only be initiated if the test is enabled in the user profile.
1.
From the Main Menu, press 1 for System Tests.
If any alarm verification zones are being used, the user will be asked if they wish to disable alarm
verification during walk test. This occurs for either walk test option.
2.
Select 3 for Walk Test-No Report. The LCD will display "WALK TEST STOPPED" on Line 1 and "ENTER
= start test" on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm (06 to 180
second), if you select this option, central station reporting will be disabled while the test is in progress.
Select 4 for Walk Test-with Report. The LCD will display "WALK TEST STOPPED" on Line 1 and
"ENTER = start test" on Line 3. Enter the time period you wish the NAC circuit to be active for each alarm
(06 to 180 seconds) If you select this option, central station reporting will occur as normal during the walk
test.
The panel generates a TEST report to the central station when the walk test begins. During a walk test, the
panel's normal fire alarm function is completely disabled, placing the panel in a local trouble condition. All
zones respond as 1-Count zones (respond when a single detector is in alarm) during a walk test. Each alarm
initiated during the walk test will be reported and stored in the event history buffer.
3.
Press ENTER to end the walk test. The system will reset. The panel will send a "TEST RESTORE" report to
the central station.
Note: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to
normal, the panel is ready to go to the next device.
10.4.7

Conduct a Communicator Test

1.
From the Main Menu, press 1 for System Tests.
Important
10-5
LS10143-001SK-E