I/O Point Control - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
1.
Select 2 for Point Functions from the Main Menu.
2.
Select 5 for SLC Multiple Device Locator.
A message similar to the one shown in Figure 13-2 will display.
3.
Press ENTER to accept, or left arrow to Exit.
If left arrow is chosen you will exit back to the Point Function menu.
If ENTER is chosen the system will cease normal operation leaving the premise
unprotected.
4.
Select the SLC loop.
5.
Enter up to 8 SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6.
Press the left arrow key to exit SLC Multiple Device Locator.
Note: Once you exit, the system will resume normal operation.
13.5.3

I/O Point Control

This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a
point's output mapping. I/O Point Control shall only be allowed to be accessed if enabled by the user profile.
Follow these steps to control an I/O point:
1.
Select 2 (Point Functions) from the Main Menu.
2.
Select 6 (I/O Point Control).
3.
Select the module the point is on.
4.
Make any selections specific to the module selected in the previous step.
5.
Use the up or down arrow key to select the point you wish to test.
6.
Press ENTER to toggle (Active/Inactive) Output.
7.
Press the left arrow key to exit.
Figure 13-2 Shut Down Warning
13-4
Testing and Troubleshooting