Point Programming For Ecs-Amp - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 for available choices, then
press ENTER.
Select a name
for the Point
Figure 9-6 Programming Points Screen for the 5496 Module
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrow key to select the type (See Figure 9-6). Then press ENTER.
7.
Press ENTER to edit point name. See Appendix B. Or, Press right arrow key to skip point name edit.
8.
Repeat Steps 1 through 7 for all points.
9.5.6

Point Programming for ECS-AMP

To program module points:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 for available choices. Then
press ENTER.
Enter Point
Select a name
for the Point
Figure 9-7 Programming Points Screen for the ECS-AMP Module
5.
Enter the point number, then press ENTER. Points 5-8 on ECS-50W or ECS-125W will not be available
unless the ECS-CE4 is installed.
6.
Press the up or down arrow key to select the type (notification or unused), then press ENTER.
7.
Press ENTER to edit point name. See Appendix B. Or Press right arrow key to skip point name edit.
8.
Repeat Steps 1 through 7 for all points.
Enter Point
Select AUX DOOR, CONSTANT, AUX POWER
RESET or AUX RESET
Select NOTIF or Unused
9-18
Programming