Honeywell IFP-2100 Installation And Operation Manual page 157

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
Type
Function
Selection
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
DETECTOR
SWITCH
FIRE TAMPER
(cont.)
MANUAL
RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
ECS TAMPER
ECS SUPER-
VISORY
CO DETECT
SWITCH
CO
SUPERVISORY
DETECT SWITCH
OUTPUT PT
AUX CONST
AUX RESET
NOTIF
AUX DOOR
Table 9-5: Programming Options for 6815 Modules
Latching Option
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see 9.3.1.2 ).
If an acknowledge switch closes when an alarm or trouble condition is
not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The
switch must be rated at 5V, 100 mA (minimum) and be used with an
EOL resistor for supervision.
Latching
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Non Latching
Latching
Non Latching
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Non Latching
Latching
Non Latching
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
Latching
Performs identically to a supervisory switch, but will be indicated as a
tamper switch on the LCD annunciator.
Non Latching
Manual release switch
Interlock release switch input.
Latching
User also has ECS Event Number 1-8 option for ECS INPUT.
Non Latching
Only available when an ECS-VCM or ECS-NVCM is installed in the
Latching
system.
Non Latching
Latching
Non Latching
CO Detector Switch
Latching
CO Supervisory Detector Switch
Non Latching
Select Group
Output point, a general use notification type. Use for driving standard
notification appliances.
Use constant power for applications that require a constant auxiliary
power source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section 4.15.5.3
for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you
were using an auxiliary power supply for door holders, you would use
this option. See Section 4.15.5.1 for a description of how this option
operates.
Comments
9-14
Programming