Editing An Amplifier; Loc Programming; Adding An Loc; Editing An Loc - Honeywell Farenhyt IFP-2000 Manual

Analog/ addressable fire system, emergency communication system
Table of Contents

Advertisement

151430-L8
11.5.2

Editing an Amplifier

When editing AMPs, the features that may be edited are: module ID, module name, ECS-CE4 installed (Yes or
No), and output voltage. To edit an existing module:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
3.
Press 1 to enter module menu.
4.
Press 1 to edit a module.
5.
Use the
or
6.
Press the right arrow

11.6 LOC Programming

LOC Priority is a programmable option for the following ECS devices:
ECS-VCM
ECS-RVM
11.6.1

Adding an LOC

To add new LOCs to the system, follow these steps:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming menu.
3.
Press 1 to enter Module menu.
4.
Press 2 to add a module.
5.
From the next screen, add either an ECS-VCM* or ECS-RVM**.
* Only 1 ECS-VCM may be installed per site.
** Up to 15 ECS-RVMs may be installed per site.
The screen will display "Adding module [#]..." for a few moments. You will be returned to the <New Mod-
ule Type> screen where you can select another a name for the module(s) if desired.
6.
Add a RA-2000-LCD Annunciator, if desired, to associate with each ECS-VCM or ECS-RVM.
You must save changes when you exit the Program Menu or the new module will not be added. For more
information see section 9.2.2.
If you Add a Module that has not been physically connected, the panel will go into trouble after it re-initializes
(when you exit the Program Menu). When the new module is attached, the trouble will restore automatically the
next time you power up the system.
11.6.2

Editing an LOC

Settings that are specific to an LOC are modified by editing the ECS-VCM or ECS-RVM expander module of the
LOC. These options include: number of switch expanders installed, microphone type, microphone gain, auxiliary
gain, tone gain, message gain, keypad priority, and associated keypad.
Note: An LOC specific name can also be editing using SKSS-2.
To edit an existing module:
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 7 for Program Menu.
arrow to select the module you wish to edit.
ENTER to move to next selection.
or
Emergency Communication System Operation
11-8