Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a designated manual release switch.
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.

Conditions Required for an Interlock Release Alert Output Activation

If any single addressable detector is activated, the "Interlock Release Alert" output will activate. This alerts the
user that the initial stages required for a release condition are present. (Also refer to Table 10-4).
Conditions required for a Detector Alarm and Interlock Release Alarm Output
Activation
If two or more addressable detectors, or a manual release switch activate, the "Detector Alarm" and "Interlock
Table 10-3: Approved Releasing Solenoids
11591
11595
11592NC
16360
Figure 10-6 Wiring Configuration for Solenoid
Important!
10-16
24 VDC
417
24 VDC
417
24 VDC
416
24VDC
500
Releasing solenoid
Use 24 VDC, UL listed
model in table 10-3
1 solenoid per circuit