LS10143-001SK-E
Table 9-6: Menu choices for Internal/External Power Module
Choices
UNUSED
B NOTIF
A NOTIF
Select Type
AUX_PWR
B SWITCH
Select Type
A SWITCH
B DETECT
A DETECT
Select Zone/Group
Edit Name
Function
Type Selections
Selections for
each Type
NOTIF OUTPUT
CONTROL CIRCUIT
Same as B NOTIF
CONSTANT
AUX RESET
AUX DOOR
AUX SYNC
MANUAL PULL
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
ECS INPUT
ECS TAMPER
ECS SUPERVISORY
Same as B SWITCH
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
User also has Supervised/
Unsupervised option
Constant auxiliary power.
Resettable auxiliary power.
Door holder auxiliary power.
Refer to comments column of
Table 9-4 for description of these options.
Latch or Non-latching feature only appears for
WATERFLOW, FIRE SUPERVISORY, FIRE
TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, ECS INPUT, ECS
TAMPER, and ECS SUPERVISORY.
User also has ECS Event Number 1-8 option for
ECS INPUT.
Only available when a ECS-VCM or ECS-
NVCM is installed in the system.
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-
wire CO Supervisory detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-
wire CO Supervisory detectors
Group or Zone selection will appear depending
on the type selected.
See Appendix B
9-16
Programming
Comments