1.
Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-56 for the location of the relay ter-
minals.
2.
Configure the relay through programming (see Section 9.5).

4.17 Remote Station Applications

4.17.1

Keltron Model 3158 Installation

The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The
3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete
information.
1.
Wire the 3158 to the control panel as shown in the connection list.
2.
Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3.
Program control panel Relay 1 for alarm.
4.
Program Flexput circuit 5 for alarm.
5.
Program Flexput circuit 6 for supervisory non latching.
Terminal #
3158 Term. 1
To Keltron receiving equipment
3158 Term. 2
To Keltron receiving equipment
3158 Term. 3
Earth ground
3158 Term. 4
Not used; no connection.
3158 Term. 5
Control panel SBUS OUT +
3158 Term. 6
Control panel SBUS OUT –
3158 Term. 7
Control panel I/O5 O
4.17.2

City Box Connection Using the 5220 Module

This section describes how to connect the control panel to a local energy municipal fire alarm box or "city box"
as required by NFPA 72 Auxiliary Protected Fire Alarm systems for fire alarm service. The city (master) box is
an enclosure that contains a manually operated transmitter used to send an alarm to the municipal
communication center which houses the central operating part of the fire alarm system.
City Box Standby Current: 0 (Notification supervision current accounted for in control panel draw.)
Alarm Current: 1 Amp for 1 second 27.2 VDC max.
The maximum coil and wire resistance (combined) must not exceed 30 ohms.
To install the 5220 for city box connection:
1.
Use one of the knockouts on the right side of the control panel to connect the 5220 using a short piece of
conduit (must not exceed 20 feet in length).
2.
Wire the 5220 to the control panel as shown in Figure 4-57. This drawing also shows how to connect the city
box coil to terminals 3 and 4 on the 5220. Do not install an EOL resistor in the terminals of the Flexput cir-
cuit used for this application.
3.
Connect earth ground wire to the 5220 chassis with mounting screw.
Table 4-6: Keltron 3158 to Control Panel Connections
Connects To
Terminal #
3158 Term. 8
3158 Term. 9
3158 Term. 10
Control panel I/O5 X
Control panel Relay 1 COM
Control panel Relay 1 NO
4-41
LS10143-001SK-E
Connects To
Control panel Relay 1 COM
Control panel I/O6 O
Control panel I/O6 X
Control panel Relay 1 NO
Control panel Trouble COM
Control panel Trouble NC