Maximum Battery Standby Load; Maximum Battery Standby Loads For 24 Hour Standby; Maximum Battery Standby Loads For 90 Hour Standby - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
3.7.5

Maximum Battery Standby Load

Table 3-5 and Table 3-6 show the standby load calculations for the IFP-2100 based on 24 and 90 hours of
standby. The standby load calculations of line D in the Current Draw Calculation Worksheet must be less than
the number shown in Table 3-5 and Table 3-6 for the selected battery size, standby hour and alarm time. The
numbers below have a built in 20% derating factor for the battery amp-hour capacity.
Table 3-5: Maximum Battery Standby Loads for 24 Hour Standby
Rechargeable
Battery Size
17AH
18AH
24AH
33AH
35AH
40AH
55AH
Table 3-6: Maximum Battery Standby Loads for 90 Hour Standby*
Rechargeable
Battery Size
33 AH
40 AH
55 AH
Honeywell Silent Knight does not support the use of batteries smaller than those listed in Table 3-5 and Table 3-6. If you
use a battery too small for the installation, the system could overload the battery resulting in the installation having less
than the required 24 hours standby power. Use Table 3-5 and Table 3-6 to calculate the correct battery amp hour rating
needed for your installation. It is recommended that you replace batteries every five years.
*For FM Installation only
24 hr Standby,
24 hr Standby,
5 mins. Alarm
15 min alarm
535 mA
569 mA
769 mA
1.07A
1.14A
1.30A
1.80A
90 hr Standby,
90 hr Standby,
5 min alarm
15 min alarm
N/A
347 mA
480 mA
Warning
3-19
24 hr Standby,
20 min alarm
473 mA
442 mA
506 mA
475 mA
706 mA
675 mA
1.01A
975 mA
1.07A
1.04A
1.24A
1.21A
1.74A
1.71A
90 hr Standby,
20 min alarm
N/A
N/A
331 mA
322 mA
464 mA
456 mA
LS10143-001SK-E