Section 4

Control Panel Installation

4.1

Mounting the Control Panel Cabinet

Read the environmental specifications in Section 3.2 before mounting the control panel cabinet. This will ensure
that you select a suitable location.
The IFP-2100 cabinet can be surface or flush mounted. Cabinet base dimensions are 24¾" H x 14.5" W. If you
flush mount there should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured from either
the top edge or bottom edge to the exterior side of the sheet rock. Do NOT flush mount in a wall designated as a
fire break.
The IFP-2100/ECS cabinet can be surface or flush mounted. Cabinet base dimensions are 26½" H x 20"W. If
you flush mount the cabinet, there should be 1.5" to 1.75" of cabinet extruding from the wall, this should be
measured from either the top edge or bottom edge to the exterior side of the sheet rock. Do NOT flush mount in
a wall designated as a fire break.
24.75"
IFP-2100
4.1.1

Preventing Water Damage

Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
26.5"
14.5"
Figure 4-1 FACP Cabinet Mounting
IFP-2100ECS
4-1
LS10143-001SK-E
20"