Number Of Answer Rings; Dial Option (Touchtone Or Pulse, Or Tt/Pl); Dial Format; Monitor Line - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
characters begin displaying after "9".
7.
Enter a dialing prefix (if needed), then press ENTER. Or Press the right arrow to bypass the dialing prefix
option.

Number of Answer Rings

This option is used in conjunction with HFSS Honeywell Fire Software Suite. Use this option to determine the
number of rings before the panel answers a call from the computer. Range is 00-15 rings. This option is factory-
programmed as 06 rings, which should be compatible for most installations where the answering machine bypass
feature is used. You may need to adjust it depending on the installation's telephone system.
The selection made here must match the programming for this option in the Communication Configuration
dialog box of HFSS.
8.
Enter the desired number of answer rings, then press ENTER.

Dial Option (TouchTone or Pulse, or TT/PL)

9.
Press the up or down arrow key to select the dial option, then press ENTER.
Dial Option
PULSE
If this option is selected, only pulse dialing will be used for this phone line.
TT
TouchTone dialing. If this option is selected, only TouchTone dialing will be used for this phone line.
TT/PL
TouchTone alternating with pulse. If this option is selected, the communicator will first attempt to use
TouchTone. It will switch to pulse if TouchTone is not successful on the first attempt. It will continue to
alternate between TT and pulse for additional attempts.

Dial Format

10. Press the up or down arrow key to select the pulse ratio for rotary dialing option, then press ENTER.
Options are:
U
E
Dial Tone Detection Disabled
11. Select Y (do disable) or N (don't disable) by pressing the up or down arrow key, then press ENTER.

Monitor Line

Enable the line monitor for each phone line that will be used. See Figure 9-9 for location of this field on the
phone lines screen. When the phone line monitor has been enabled for a phone line, a trouble condition will
occur if the line is not connected. If a phone line will not be used, it must be disabled.
12. Select Y (monitor line) or N (don't monitor line) by pressing the up or down arrow key, then press ENTER.
Answering Machine Bypass
This option is used in conjunction with HFSS Honeywell Fire Software Suite. This feature ensures that an
answering machine will not interfere with communication between the panel and the computer. If an answering
machine is used at the panel site, enable this feature; if an answering machine is not used, disable the feature.
This option is factory-programmed as No (disabled).
The selection made here must match the programming for this option in the Communication Configuration
dialog box of HFSS.
U.S. standard format. Uses the 60 msec / 40 msec make/break ratio.
European format. Uses the 66 msec / 34 msec make/break ratio.
9-23
Description
LS10143-001SK-E