Fire Page; Emergency Page; Paging; Custom Ecs Event - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
11.7.2

Custom ECS Event

This event is activated by gaining ECS Control at a LOC and using the microphone without any ECS event
already active in the Manual ECS State. In this case, the Mic Triggered ECS Alarm mapping and General ECS
Alarm mapping will be activated and stay activated until a different ECS event is activated at the LOC or the user
resets the Emergency Communication System.
11.7.3

Fire Page

A fire page can only occur when:
1.
Only the fire system is active.
2.
Both fire and the emergency systems are active and the highest priority active fire event is programmed to be
of higher priority than the highest priority active emergency event.
3.
Only the fire system is active, the user has gained ECS Control, and custom ECS event is a lower priority
than the fire alarm.
Note: If fire and emergency systems are active and emergency system is of a higher priority, a fire page is NOT
allowed. An LOC must gain ECS Control in order to do any live voice.
11.7.4

Emergency Page

An emergency page can occur when:
1.
Only the emergency system is active and the user has gained ECS Control.
2.
Both fire and the emergency systems are active and the highest priority active emergency event is pro-
grammed to be of higher priority than the highest priority active fire event and the user has gained ECS Con-
trol.
3.
Only fire system is active, the Emergency LOC Alarm priority is higher than the active fire system event and
the user has gained ECS Control.
This will trigger the ECS system and enable mapping for 'Mic Triggered ECS Alarm'
and 'General ECS Alarm'.

11.7.4.1 Paging

If there are no active emergency or fire system events, the microphone at an LOC can be used for paging by
following these steps:
1.
Push the PTT (push to talk) button on the microphone.
2.
Use the Select Keys on the LOC to toggle the output areas to page to with the microphone (illuminates the
green LEDs).
Note: The Ready to Talk LED will illuminate after an output area has been activated.
3.
Speak into the microphone.
4.
Release PTT button when finished.
Emergency Communication System Operation
11-10