Ecs Super User; Exit Ecs Control Menu; Relinquish Ecs Control; Ecs Reset - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
request for ECS Control is automatically made. Additionally, the lockout timer does not apply for ECS Super
User.
When a request for ECS Control is made, the LOC with ECS Control will be shown a screen (similar to Figure
11-3), even when in another menu, except programming menus, indicating that another LOC is requesting ECS
Control. The piezo buzzer on the LOC with ECS Control sound when an ECS Control request is active to alert a
nearby operator of the request.
Figure 11-3 ECS Control Request on LOC with ECS Control
Once ECS Control is passed to another LOC, the new user will assume the system AS IS. This means that the
event that was set to be playing at the previous LOC and all output areas it was playing in do not change.
11.2.8

Exit ECS Control Menu

The user can exit the LOC ECS interface by pressing the left arrow key. The user will be returned to the idle
screen which indicates that the LOC still has ECS control.
11.2.9

Relinquish ECS Control

Relinquishing ECS Control is accomplished by pressing the ECS Control Key from within Message Mode. A
screen will be displayed to ensure the user wants to relinquish ECS Control. ECS Control will be automatically
relinquished after a time-out on this screen. When ECS Control is relinquished, the system stays in the Manual
ECS State. ECS Control can then be gained by another LOC or again at the same LOC.

11.2.10 ECS Reset

An ECS reset is accomplished by pressing the RESET button from an LOC. The user will be prompted to reset
either the fire system or emergency system. After an ECS reset, the LOC will automatically exit the LOC ECS
interface.
Note: In order to perform an ECS reset, the display must be associated with the ECS-VCM or ECS-NVCM / ECS-
RVM. See Section 11.6.2.2.

11.3 ECS Super User

The ECS Super User access code profile function provides the ability to override all ECS Control rules and gain
ECS Control. The ECS Super User is the highest priority user in the system. The ECS Super User has several