Honeywell IFP-2100 Installation And Operation Manual page 122

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
8.
Select one of the following options from the menu that displays.
1 - Review System
Press 1 if you need to review the JumpStart configuration. The Review System menu will appear. Press 1
to review Entire System or Press 2 for Changes Only.
2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason.
1. If you are ready to make the JumpStart
2. The system will ask you if the installation contains any addressable duct detectors. If there are none,
select 2 for No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and con-
tinue with Step 3.
3. From the list that displays, select the SLC that contains the duct detectors.
4. The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and 2
for NonDUCT.
5. Press up arrow to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until
3 - Accept Changes
all duct detectors have been selected. (Note: You can move backwards through the list with down
arrow).
6. When you reach the last detector on this device, press left arrow.
7. The system will ask you if there are any duct detectors used. If there are, select 1 for Yes and the
message will ask, Have All Addressable Duct Detectors Been Identified? Left arrow for "No",
Right arrow for "Yes". If there are no more duct detectors, continue with Step 8.
8. The system will restart with the saved JumpStart configuration.
9. After the system resets, it will use the new JumpStart configuration.
4 - Discard Changes
If you want to discard the changes, and keep the configuration you had before running this JumpStart
press 4.
®
configuration permanent, select 3.
8-3
LS10143-001SK-E