Honeywell IFP-2100 Installation And Operation Manual page 50

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
The total worst case current is calculated as follows:
RA-2000 Current Draw
RPS-1000 Current Draw
5865 Current Draw
5824 Current Draw
Total Worst Case Current Draw
Note: For assistance with SBUS calculation, please refer to www.farenhyt.com.
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
= 2 x .120 amps
= .240 amps
= 1 x .010 amps
= .010 amps
= 1 x .200 amps
= .200 amps
= 1 x .040 amps
= .040 amps
= .490 amps
4-8
Control Panel Installation