Temporary Connection Of Detector Base To Panel For Addressing - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
1.
Connect a detector base temporarily to the programming terminals as shown in
Figure 7-6. (You can use the same base for each detector.)
Figure 7-6 Temporary Connection of Detector Base to Panel for Addressing
2.
Enter the Installer Code. The panel will automatically go to the main menu.
3.
Select 2 for Point Functions.
4.
Select 3 for Set SLC Dev Addr.
5.
Select "Yes" by pressing the up arrow, then press ENTER. (The panel will go into trouble at this point. You
can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel re-initializes
when you finish programming.)
6.
When the wait message clears, the following options display:
1. for Read Address. Use to read (or check) a single detector's address.
2. for Write Address. Use to program a single detector's address.
3. for Seq. Programming. Use to program more than one detector in sequential order.
7.
If you are changing addresses, write the programmed address on the back of the device.
8.
To exit press left arrow until fully exited.
7-9
LS10143-001SK-E