Ul 864 / Ul 2572 Programming Requirements - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
Section 9
Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator.
Each subsection discusses these menu options in detail. All options described in this section can be performed
using the HFSS - Honeywell Fire Software Suite.
Before any customized programming is done, JumpStart AutoProgramming should be run first. After
JumpStart is run, thoroughly test the system. The reason the system should be tested after JumpStart
AutoProgramming is because JumpStart AutoProgramming automatically programs the system, searching for
and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed. Refer to Section 8.
9.1

UL 864 / UL 2572 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in
the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, and Stand for Mass Notifications
Systems, UL 2572, certain programming features or options must be limited to specific values or not used at all as
Programming
Menu Item
Option
Time Options
Auto-resound
Time Options
Low AC
Report Delay
Display Oldest
Y (Enabled)
Event
N (Disabled)
Initial Delay
0-28
Inter Message Delay 4-32
Alarm Verification
Alarm
Verification
Auto Reset ECS
Auto Reset
MIC Triggered Event
ECS Custom
Event
ECS Input
ECS Input
Event Priority
CO Alarm
Important!
indicated below.
Permitted in
Permitted in
UL 864
UL 2572
(Y/N)
(Y/N)
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
9-1
Settings
Possible
Permitted in UL
Settings
864
4 hrs, 24hrs
4 hours if using
SWIFT devices
0–30 hours
1–3
Yes & No
Yes
Yes & No
No
0-28
3
4-32
4-32
60-250
60
(confirmation
period)
Never
Never
Timer Event
Timer Event
Disabled
Disabled
Latching
Latching
Non-Latching
Yes & No
No
LS10143-001SK-E
Settings
Permitted in
UL 2572
4 hours if using
SWIFT devices
1–3
Yes
No
3
4-28
60
Never
Timer Event
Disabled
Latching
No