Installing 2-Wire Class B Smoke Detectors; Installing 2-Wire Class A Smoke Detectors - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual

4.15.3.1 Installing 2-Wire Class B Smoke Detectors

To install a Class B two-wire smoke detector, wire as shown in Figure 4-51.
EOL 4.7 k Ω
Any 2 wire
smoke detector
listed in Appendix A

4.15.3.2 Installing 2-Wire Class A Smoke Detectors

To install a Class A two-wire smoke detector, wire as shown in Figure 4-52.
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Figure 4-52 Two-Wire Class A Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-52 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
4.15.4
Installing 4-Wire Smoke Detectors
Any compatible UL listed four-wire smoke detector can be used with the control panel (see Appendix A for list
of compatible smoke detectors). Figure 4-53 and Figure 4-54 illustrate how to connect a UL listed four-wire
Maximum Impedance per circuit is 50Ω
Figure 4-51 Two-Wire Class B Smoke Detector
Maximum Impedance per circuit is 50
supervised
power limited
Note:
Flexput circuit 5
used as an example.
Any Flexput circuit
could be used.
supervised
power limited
Any 2 wire
smoke detector
listed in
Appendix A
Ω