Operation Mode Behavior; Highest Priority Event Display; Event Display After Two Minutes Sitting Idle - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
gets priority. Example: Template 1 Contains Group 1. Zone 1 Manual Pull is mapped to Template 1 and
Group 1 using constant and ANSI patterns respectively. If Zone 1 Manual Pull is active, Group 1 will output
ANSI.
When an event is mapped to an output group from multiple zones, the lower numbered zone gets priority.
Example: Zone 1 Manual Pull and Zone 2 Manual Pull are mapped to Group 1 using constant and ANSI
patterns respectively. If Zone 1 and Zone 2 Manual Pull events are active, Group 1 will output constant.
Note: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the Sys-
tem Status event priority.
Note: All fire, emergency and system troubles are prioritized into the Trouble event priority.

10.6 Operation Mode Behavior

The control panel can be in one or more of seven conditions at any given moment: Normal, Alarm, Prealarm,
Supervisory, Trouble, Silenced, and Reset. Table 10-2 describes the behavior of the panel in each of these modes.
When looking at the LCD, the screen will display FS for the "Fire System", or CO for the "CO System". The
highest priority event will display first and include the event count (see Figure 10-4).
Press the down arrow to view the location and type of alarm supervisory or trouble. If the panel is programmed to
Auto Display Event, information describing the highest priority active event will display on the first two lines.
site
Figure 10-5 Event Display after Two Minutes Sitting idle
Figure 10-4 Highest Priority Event Display
panel#
10-11
module#
LS10143-001SK-E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents