Honeywell IFP-2100 Installation And Operation Manual page 255

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Operation
Silence Alarms and
Press SILENCE then enter a code if prompted. Silence LED will light.
Troubles
Reset Alarms
Press RESET then enter a code if prompted.
For each type of condition, press the up or down arrow associated with Alarm, Supervisory, or Trouble.
View Alarms,
Supervisories, and
Troubles
View status of Point
Hold the DRILL button and then enter a code if prompted. OR
Conduct a Fire Drill
Check Detector
Sensitivity
Set Time and Date
Enable / Disable a Point
View Event History
For Service call:
Model IFP-2100 Basic Operating Instructions
These instructions must be framed and displayed next to the IFP-2100
panel in accordance with NFPA 72 fire code for Local Protected Fire
Alarm Systems. Test the system in accordance to NFPA 72.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Press 2 to select Point Functions.
3.
Enter code if prompted, then press 2 to select Point Status.
4.
Select the module the device is located on by using the up or down arrow. Then press ENTER.
5.
Enter the point number.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Press 1 to select System Tests.
3.
Enter code if prompted, then press 1 to select Fire Drill.
4.
Press ENTER to start the fire drill., and Press ENTER to end the fire drill.
1.
Follow steps 1 through 5 for viewing a point's status.
2.
Press the right arrow to view detector sensitivity.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Press 4 to select Set Time & Date. Enter a code if prompted.
3.
Make changes to the fields on the screen as necessary.
4.
Press ENTER if you wish to keep the changes.
5.
Press ENTER to set the entered time and date.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Press 2 to select Point Functions.
3.
Press 1 to select Disable / Enable Point.
4.
Press 7 to select Disable/Enable Point.
5.
Select the module the point is located on by using the up or down arrow. Then press ENTER.
6.
Enter the point number then press ENTER.
7.
Press the right arrow to Disable/Enable Point.
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Press 3 to select Event History.
3.
Enter code if prompted.
4.
Press the up or down arrow to view events in the history buffer.
Task to Perform
P/N LS10149-001SK-E Rev A
ECN: 16-0218

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents