Gaining Ecs Control; Loc Priority; Loc Lockout - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
Select LEDs
Select Keys
Figure 11-1 ECS-VCM or ECS-NVCM / ECS-RVM Front View
11.2.2

Gaining ECS Control

When attempting to gain ECS Control, there are three things that govern whether or not ECS Control can be
obtained:
1.

LOC Priority.

2.

LOC Lockout.

3.
User profile access control.
11.2.2.1 LOC Priority
LOCs are assigned (through panel or HFSS Honeywell Fire Software Suite of the ECS-VCM, ECS-NVCM or
ECS-RVM) an LOC priority of low, normal, or high. LOCs with a higher priority are always able to gain control
from a lower priority LOC.
11.2.2.2 LOC Lockout
When LOCs are programmed to the same priority, the setting LOC lockout applies. LOC lockout will not allow
an LOC to gain ECS Control from the LOC with ECS Control until one of three things happen:
1.
The LOC lockout timer expires. Once the LOC lockout timer expires, an attempt to gain ECS Control can be
made again.
NON-ACTIVE CALL
ALL CALL
Key
Key
11-3
LS10143-001SK-E
ECS Control
ECS Control LED
Key
Message Keys
Message LEDs