Defining Output Group Type; Silencing Options; Corresponding Key And Led For Mapping Output Groups - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

LS10143-001SK-E
Template Override is shown when set to Yes.
Dynamic Activation -Is shown if a non-voice group is assigned to a Select/Dynamic Activation switch
number
Dynamic Activation / Template Override Cadence. (This is shown when the Template override is set to Yes
and Dynamic Activation is Yes): this setting sets the cadence of the non-voice group mapped to voice select
switch when activated using dynamic activation or by a template. See Sections 11.2.3.2 and 9.4.3 for more
information.

Defining Output Group Type

Each output group is defined as either a voice output group or a non-voice output group. Output points that are
audio circuits (all circuits on the ECS-50W, ECS-125W, ECS-DUAL50W, ECS-INT50W and ECS-CE4) can
only be assigned to voice output groups. Output points that are non-voice circuits (all other points and circuits
that are on all modules except the ECS-50W, ECS-125W, ECS-DUAL50W, ECS-INT50W and ECS-CE4) are
assigned to non-voice output groups.
Each of the output groups defined as voice can be mapped to a particular switch and LED on the ECS-VCM/
ECS-NVMC, ECS-RVM and ECS-SW24. This allows the user to see the state of the voice groups assigned to the
switches.
This also lets the user individually select which areas they want to do a live page into. Output groups not defined
as voice groups can also be assigned to these switches as long as there is a voice group already assigned to the
group. This allows for dynamically activating/deactivating both voice and strobes/other outputs in an area with a
single button press. See 11.2.3.2.
Key and LED Numbers
Figure 9-3 Corresponding Key and LED for Mapping Output Groups

Silencing Options

The following silencing options are available for each output group.
Optional
Timers
Silence Inhibit
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Auto Silence
Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
Corresponding
ECS User Interface
Table 9-3: Silencing Options
Corresponding
Key and LED Numbers
ECS-SW24
Description
9-8
Programming

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents