Requirements For Remote Station Protected Fire Alarm Systems; Requirements For The Installation Of Carbon Monoxide (Co) Detection And Warning Equipment, Nfpa 720; Nfpa Requirements - Honeywell IFP-2100 Installation And Operation Manual

Analog/addressable fire system emergency communication system
Hide thumbs Also See for IFP-2100:
Table of Contents

Advertisement

Model IFP-2100/ECS Installation Manual
P.A.S. (positive alarm sequence) feature shall be used only with automatic detectors.
2.2.2
Requirements for Central Station Fire Alarm Systems
1.
Use both phone lines. Enable phone line monitors for both lines.
2.
You must program a phone number and a test time so that the IFP-2100/ECS shall automatically initiate and
complete a test signal transmission sequence to its associated receiver at least once every 6 hrs.
3.
The AC Loss Hours option must be set from 1-3 hours.
4.
If using wired Ethernet or cellular, you must program the corresponding account/subscriber ID and a test
time so that the FACP shall automatically initiate a test signal transmission sequence to its associated
receiver at least once every 6hrs.
2.2.3
Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliance must be used.
2.2.4
Requirements for Remote Station Protected Fire Alarm
Systems
Minimum system requirements are one Honeywell Silent Knight addressable initiating device and wither a 5220,
Keltron 3158 or the built-in Digital Alarm Communicator Transmitter (DACT).
1.
Do not exceed the current draw load restrictions shown in Section 3.7.
2.
The AC Loss Hours option must be set from 1-3 hours.
2.2.5
Requirements for the Installation of Carbon Monoxide (CO)
Detection and Warning Equipment, NFPA 720
When using carbon monoxide detection the system must be monitored by a Supervising Station.
2.2.6

NFPA Requirements

The following is the minimum configuration to meet the NFPA requirements.
Model/
Module
021000
RFP-2100
Cell-Mod
5220
5815XL
5824
7644
6815
SK-NIC
SK-FML
NFPA Requirements for IFP-2100 or RFP-2100
Table 2-1
Description
Local
Motherboard
Y
Remote unit
O (1)
Transmitter
O
Rev Pol Mod
O
SLC Exp
O
Serial card
O
Rev pol mod
O
SLC Exp
O
Network card
O
Fiber module
O
Remote
Releasing Auxiliary
Y
Y
O (1)
O (1)
O
O
O
Y
O
O
O
O
O
N
O
O
O
O
O
O
2-3
LS10143-001SK-E
Central
Station
Station
Y
Y
O (1)
O (1)
O
O
Y
O
O
O
O
O
Y
O
O
O
O
O
O
O

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp-2100ecsRfp-2100

Table of Contents