7000 "A" Frame

Filter Capacitors

Filter capacitors are used on the motor side for all drives. The AFE
rectifier option also includes filter capacitors on the line side. Refer to
Figure 4.17 (DC Link and Fan Cabinet with control panel removed).
The filter capacitors are three-phase four-bushing units and "oil-filled".
The three-phase capacitors are comprised of internal single-phase units
that are connected in a Y configuration. The neutral point of the Y is
connected to the fourth bushing, which is accessible and can be used for
neutral point voltage measurement or other protection/diagnostics purposes.
Depending on the drive configuration, the fourth bushing may or may not
be connected to circuitry. The metal cases of the capacitors are grounded
through a stud on the capacitor housing.
The capacitors are equipped with internal "bleeding resistors" to discharge
the capacitor and reduce its voltage below 50V in 5 minutes when left
disconnected. A typical three-phase capacitor is shown below:
Line Filter Capacitor
(with AFE Rectifier only)
Figure 4.18 – Motor Filter Capacitor
Allow 5-10 minutes for motor capacitors to
W A R N I N G
W A R N I N G
safely discharge voltage prior to opening cabinet
doors.
Component Definition and Maintenance
7000A-UM151E-EN-P - October 2018
4-21
Motor Filter
Capacitor