View Drive Status

View and Reset Alarms

7000 "A" Frame
The status of the drive is viewed by pressing the [F7] key from the
Top Level Menu. This screen, shown in Figure 3.73, constantly
displays the latest status of the drive.
Figure 3.73 – Status Screen
All drive faults and warnings are logged to their respective queues.
Collectively the faults and warnings are referred to as "Alarms".
When a new alarm occurs, the F6 key on any screen will begin to
flash in reverse video. Pressing the [F6] key on any screen will bring
you to the screen as shown in Figure 3.74.
Figure 3.74 – Alarm Summary Screen
The screen shows the current status of the drive, as well as the last
active Fault that tripped the drive and any pending warning. (The
screen only shows a fault and/or warning if the drive is still in the fault
and/or warning state. This is independent of the content of the queues.)
Note: Terminal FRN > 4.005.
To aid in troubleshooting, a time and date stamp is also provided,
indicating the last time the drive was started and stopped for any
reason.
To acknowledge the alarm(s), press the [F6] key. This will cause the
F6 key to cease flashing and return to normal video. (If a new alarm
were to occur, the F6 key would again flash in reverse video).
Operator Interface
3-53
7000A-UM151E-EN-P - October 2018