Operator Interface
3-43
state of fault masks currently displayed, press the [F7]. Each press of
the [F7] key will toggle the screen to show the masks in the other state.
To change the state of a mask on the FAULTS OVERVIEW screen,
use the [cursor up] and [cursor down] keys to select the desired mask
and press the [enter] key. In the example of Figure 3.52, the "AC
O/V" is currently disabled and is selected. When [enter] is pressed
its mask is enabled, thus removing the fault from this screen as
shown in Figure 3.54. Pressing [F7] toggles the screen to show the
enabled faults, which the AC O/V is one of (Figure 3.55). (If
nothing happens, you do not have proper access to the drive. Exit to
the SETUP screen and refer to the section entitled Enter/Modify an
Access Level to gain access).
Figure 3.54 – AC O/V Removed From List
Figure 3.55 – AC O/V Now Enabled
The changes to the fault masks do not take effect until the screen is
exited via the [F10] key, i.e. exiting the FAULTS OVERVIEW will
change the masks in the drive as will exiting the FAULTS SETUP
screen. In our example, exiting the FAULTS OVERVIEW screen
and returning to the FAULTS SETUP screen now shows the "AC
O/V" mask as being ON (Figure 3.56).
7000 "A" Frame
7000A-UM151E-EN-P - October 2018