Allen-Bradley PowerFlex 7000 User Manual page 106

Medium voltage ac drive air-cooled (‘a’ frame) – forge control
Hide thumbs Also See for PowerFlex 7000:
Table of Contents

Advertisement

3-46
Operator Interface
7000A-UM151E-EN-P - October 2018
The layout of the PLC 'rack' is dependent on the DIP switch settings
on the RIO adapter, (refer to the appropriate manual for information
on the following adapters and their use: 1203-GD1, 1203-GK1,
1203-CN1, 1203-GD2, 1203-GK2, 1203-GK5, 1203-GU6, 1203-
SM1 and 1203-SSS). Tags are assigned to rack module locations in
pairs. These pairs are referred to as links and consist of two input
and two output words. There are a total of four links that can be
assigned to the RIO adapter.
The screens show the current tags and their tag code, which are
associated with each of the links. To change the tag attached to a
link, use the [cursor up] and [cursor down] keys to highlight the
desired link and press the [enter] key. (If nothing happens then you
have not gained the required access to make changes. Exit to the
SETUP screen and refer to the section entitled Enter/Modify an
Access Level to gain access).
Figure 3.60 – PLC Input Links
Figure 3.61 – PLC Output Links
This will begin the selection process of a tag as described in the
section entitled "Select a Parameter". When selecting a tag for the
output words, only parameters will be allowed. Both parameters and
read-only parameters are allowed for the selection of input words.
When you have completed the selection process, the selected tag will
be assigned to the link. To remove an assignment to the highlighted
link, press the [delete] (Backspace) key.
7000 "A" Frame

Advertisement

Table of Contents
loading