Filter Mounting - Allen-Bradley 1305-RFB-5-A User Manual
The input rfi filter units are designed to be used with the following adjustable frequency ac drives:
1305;
1336 plus;
1336 plus ii;
1336 force;
1336 impact
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate.
2
Refer to the Filter Selection table on page 5 for frame references and corresponding catalog numbers.
Filter Mounting
Series B Filters can be mounted using either method