Loading Programs (Firmware) - Allen-Bradley PowerFlex 7000 User Manual

Medium voltage ac drive air-cooled (‘a’ frame) – forge control
Hide thumbs Also See for PowerFlex 7000:
Table of Contents

Advertisement

3-56
Operator Interface
Loading Programs
(Firmware)
7000A-UM151E-EN-P - October 2018
Figure 3.78 – Typical Printer Screen
Firmware is the program that is run in the operator interface to
provide all the functionality described in this manual. Firmware is
loaded from the flash card in one of two ways.
a) If an operator interface has a memory card inserted when it is
powered up or rebooted, and that card has a valid firmware file
with the extension of .FMW, the operator interface will
automatically load the first .FMW file it encounters on the card.
b) The user can select from one or more .FMW files on the card and
load the selected firmware into the operator interface. This is the
method that will be described here.
From the TRANSFER screen, press the [F3] key. The operator
interface will enter the DIRECTORY screen from which an existing
firmware filename can be selected or entered. Refer to the sections
entitled "Select a filename" and "Enter a filename". (If nothing
happens then you have not gained the required access to modify the
flash memory. Exit to the TRANSFER screen and refer to the
section entitled Enter/Modify an Access Level to gain access).
When the filename has been obtained, the TRANSFER: PROGRAM
screen such as that in Figure 3.79 will be displayed, showing the
filename, indicating the operation you are about to perform and
showing the current status of the operation.