AH 5 00 Pr ogr am m ing Ma n ua l
Socket number
8. Generally, the pulse instruction SCLOSEP is used.
Example:
Please refer to the example of the execution of SOPEN.
Additional remark:
1.
If S
, or S
exceeds the range, the instruction is not executed, SM0 is ON, and the error code
1
2
in SR0 is 16#2003.
2.
During the closing of the connection, if the computer as the client abandons the connection,
the error occurs, the corresponding error flag is ON, and the error code is 16#6214. During the
connection, if there is a response timeout, the error occurs, the corresponding error flag is ON,
and the error code is 16#6212.
3.
When executing this instruction, if the network cable is not connected, SM1100 will be ON and
the error code is 16#600D.