Example 2:
b15
b8
b7
D20
16#31(1)
D21
16#33(3)
D22
16#35(5)
16#36(6)
D23
16#38(8)
D24
D25
16#00
Additional remark:
1.
If the number of characters contained in the string in S exceeds the range, the instruction is not
executed, SM0 is ON, and the error code in SR0 is 16#2003.
2.
If the sign code in S is not 16#20, 16#2B, 16#30 and 16#2D, the instruction is not executed,
SM0 is ON, and the error code in SR0 is 16#2003.
3.
If the decimal point in the string in S is not stored between the first character after the sign
character and the last character, the instruction is not executed, SM0 is ON, and the error code
in SR0 is 16#2003.
4.
If the binary number converted from the string in S exceeds the range, the instruction is not
executed, SM0 is ON, and the error code in SR0 is 16#2003.
5.
In the string in S, except for the sign code, the code representing the decimal point, and the
code which can be ignored, i.e. 16#20 or 16#30, the other codes have to be within the range
between 16#30 and 16#39. If the other codes are not within the range between 16#30 and
16#39, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003.
6.
If the operand D
used during the execution of the 16-bit instruction is declared in ISPSoft, the
1
data type will be ARRAY [2] of WORD/INT.
7.
If the operand D
used during the execution of the 32-bit instruction is declared in ISPSoft, the
1
data type will be ARRAY [2] of DWORD/DINT.
6 - 4 6 6
b0
16#20( )
16#32(2)
16#34(4)
16#2E(.)
16#37(7)
( D11,D10)
Number of characters
10
(D13,D12)
Number of dec imal plac es
3
(D1,D0)
12345678