AH 5 00 Pr ogr am m ing Ma n ua l
API
Instruction code
1219
BRST
Device X
Y
M
D
n
Symbol:
Explanation:
1.
The instruction is used to set the n
2.
When the instruction BRST is driven, the specified bit is set to OFF.
3.
The operand n should be within the range between 0 and 15.
Example:
When X0.0 is ON, the ninth bit in D10 is set to 0.
Additional remark:
If n is less than 0, or if n is larger than 15, the instruction is not executed, SM0 is ON, and the error
code in SR0 is 16#200B.
6 - 2 9 6
Operand
D, n
P
S
T
C
HC
D
Pulse instruction 16-bit instruction (5 steps) 32-bit instruction
AH500
D : Device number
n : Bit number
th
bit in the register specified by D to 0.
b15
1 1 1 1 1 1
1
After the instruction
is executed
b15
1 1 1 1 1 1
0
Resetting the bit in the word device
L
SM SR
E
PR
AH500
Word
Word
D10
b0
1 1 1 0 0 0 0 1 1
D10
b0
1 1 1 1 0 0 0 1 1