API
Instruction code
0304
BMOV
Device X
Y
M
S
D
n
Symbol:
Explanation:
1.
n pieces of data in devices starting from the device specified by S are transferred to the
devices starting from the device specified by D.
2.
The operand n should be within the range between 1 and 256.
3.
In order to prevent the error which results from the overlap between the source devices and
the destination devices, the data is transferred in the following way.
When the device number of S is larger than the device number of D, the data is transferred in
the order from
to
When the device number of S is less than the device number of D, the data is transferred in
the order from
to
Example 1:
When X0.0 is ON, the data in D0~D3 is transferred to D20~D23.
Operand
S, D, n
P
S
T
C
HC
D
Pulse instruction 16-bit instruction (7 steps) 32-bit instruction
AH500
S : Data source
D : Data destination
n : Data length
.
1
D 20
2
D 21
3
D 22
.
1
D 19
2
D 20
3
D 21
Ch a pt er 6 Ap p l i ed I ns t r uc t i ons
Transferring all data
L
SM SR
E
PR
AH500
Word
Word
Word
D 19
D 20
D 21
D 20
D 21
D 22
Function
K
16# "$"
DF
6 - 1 2 1