AH 5 00 Pr ogr am m ing Ma n ua l
composed of X0.0~X0.7 and Y0.0~Y0.7. The corresponding internal relays of the 16 switches
are M10~M17 and M20~M27.
X0.0 X0.1 X0.2 X0.3 X0.4 X0.5
3.
The eight input devices starting from X0.0 are connected to the two output devices starting
from Y0.0 to form the two rows of switches. The states of the two rows of switches are read in
the matrix scan, and stored in the devices starting from M10 specified by D
of the first row of switches are stored in M10~M17, and the states of the second row of
switches are stored in M20~M27.
Additional remark:
1.
If S+7, D
+n-1, or D
1
ON, and the error code in SR0 is 16#2003.
2.
If n is less than 2, or if n is larger than 8, the instruction is not executed, SM0 is ON, and the
error code in SR0 is 16#200B.
3.
If users declare the operand S in ISPSoft, the data type will be ARRAY [8] of BOOL.
6 - 1 6 4
M20
M21
M22
M23
X0.1
X0.2
X0.3
X0.4
M10
M11
M12
M13
T he first row of i nput s ignals ar e r ead.
Y0.0
1
3
T he second r ow of input s ignal s ar e read.
Y0.1
2
+(n*8)-1 exceeds the device range, the instruction is not executed, SM0 is
2
M24
M25
M26
M27
X0.5
X0.6
X0.7
M14
M15
M16
M17
X0.6
X0.7
4
Y0.1
Y0.0
. That is, the states
2